Flame Scanners

Date:2017-10-18     Hits:6261

The Fireye InSight Type 95IR, 95UV, and 95DS flame scanners are microprocessor based flame scanners utilizing solid state infrared (IR), ultraviolet (UV) or dual (IR and UV) sensors. 

INTEGRATED FLAME SCANNER
with INTERNAL FLAME RELAY
Type 95IR/95UV/95DS
The FIREYE InSight Type 95IR, 95UV, and 95DS flame
scanners are micro-processor based flame scanners
utilizing solid state infrared (IR), ultraviolet (UV)
or dual (IR and UV) sensors.
The FIREYE InSight Type 95 flame scanners incorporate
an internal flame relay with adjustable
ON/OFF thresholds, thereby eliminating the need
for a remote flame amplifier.
All FIREYE InSight scanner models are powered by
24 Vdc, have either a twelve-pin electrical quickdisconnect
or 10 ft. cable (“CG” models), and
contain electronic self-checking (no mechanical shutter required). The scanners contain an eight character
alpha-numeric LED display and a four push-button keypad to enable the user to view operating
parameters and select setpoints.


INSIGHT SCANNER SPECIFICATIONS
MECHANICAL:
Housing Material: Cast aluminum with gray polyester powder coat finish
Housing Weight: 4.3 lbs (1.96kg) or 5.9 lbs. (2.70kg) “CG” models, flange additional
Environmental: NEMA 4X, IP66, Class 1 division II Groups A, B, C, D Hazardous areas
Mounting: Requires one of two threaded mounting flanges, ordered separately (see below)
Mounting Flanges: P/N 60-2692 - 1" NPT female pipe mount with 3/8" NPT female cooling air connection,
includes 1" NPT x 3" long heat insulating nipple (P/N 35-127-1)
P/N 60-2693 - 1" BSP female pipe mount with 3/8" BSP female cooling air connection, includes
1" BSP x 3" long heat insulating nipple (P/N 35-127-3)
Mounting Flange Weight: 0.62 lbs (0.28kg)
Cooling / Purge Air Requirements: Source: Clean, dry, cool
Volume: 4 SCFM (113 l/min) at 3/8" threaded mounting flange, or 1 inch “Y” fitting,
mounted on scanner sight pipe. Temperature near the upper limit of the scanner operating
range and/or use with dirty/dusty fuels may require up to 15 SCFM (425 l/min).
Pressure: Adequate to overcome furnace or windbox pressure
Temperature Rating: -40° F to + 150°F (-40°C to +65°C)
Humidity: 0% to 95% relative humidity, non-condensing
ELECTRICAL:
Input Power: 24 Vdc, +10%, -15% supply current 0.35 A, 8.5 VA
Electrical Connection: 12-pin quarter-turn quick-disconnect or 10 ft. (3m) captive cable (“CG” models)
Relay Output: FLAME RELAY, SPST (N.O.)
FAULT RELAY, SPST (N.C.)
Contact Rating: Minimum: 10 mA @ 5 Vdc
Maximum: 2 A @ 30 Vdc
2 A @ 50 Vac (CE approved non ”CG” models)
2 A @ 240 Vac (all FM and CSA models, all”CG” models)
Analog Output: 4-20 mA dc current, referenced to 24 Vdc common, maximum connected load: 750 ohms
Status Indication: Eight (8) character alpha-numeric LED display (scrolling capability)
Operator Interface: Four (4) pushbutton style keys
Cable Specification: P/N 59-497:
Multi-core, 12 conductor (color coded), with overall braided shield
Six #18 AWG and four #22 AWG conductors, plus one #22 AWG twisted pair
Cable Jacket: Irradiated Modified Polyolefin (flame-retardant, low smoke, zero halogen)
Nominal O.D. 0.41" (10.4 mm)
Maximum O.D. 0.43" (10.9 mm)
Maximum cable length 1000 feet (305 meters)


InSight II Scanner Bulletins
Pub No.
Product
CU-113 TYPE 95DSS3-1/95DSS3-1CEX
Integrated Flame Scanner with Internal Flame Relay CU-116 95DISP-1 DISPLAY MODULE and 95WIDISP-2 IR TRANSMITTER MODULE For use with 95DSS3 InSight II Integrated Flame Scanner
CU-117 Installation Instructions - FIBER OPTICS for INSIGHT II FLAME SCANNERS 133-735 WIRELESS HANDHELD COMMISSIONING TOOL
P/N 95WIHH-2
133-739 Installation and Removal instructions for 29-431 LOCKOUT DEVICE ON 59-546 & 59-547 CABLES UC-4851 UC485 Optically isolated USB to RS422/RS485 converter
133-730 59-4647-10TB
Conversion Box for InSight I to InSight II Scanners 133-743 59-4650-10TB wiring harness for InSight II scanners
133-749 Cooling Cover P/N 60-2930-1 for InSight II CU-118 New Compact Size 24 VOLT DC POWER SUPPLY P/N 60-2685-25 - P/N 60-2685-50 DIN Rail Mounted RoHS - Compliant
CU-103 Scanner Insulating Jacket & Vortex-tube Cooler Kit CU-109 Fireye ExplorerCommunication Software For Fireye Flame Scanners with communication facilities (XP & Win 7)
133-758 60-2938-2 replacement electronics assembly for InSight II 95DSS3-1CEXSS and 95DSS3-1CEX-2

InSight I Scanners
Pub No.
Product
CU-95 Insight Integrated Flame Scanner, 95IRS2, 95UVS2, 95DSS2, 95IRS2E, 95UVS2E, 95DSS2E, 60-2721, 60-2692, 60-2693 CU-96 Pre-Wired Cable with Connector, 59-497
CU-97 Wiring Harness for Insight Scanner, 61-6944 CU-100 24 Volt Power Supply, 60-2685-2, 60-2685-4 (Obsolete)
CU-101 Installation instructions for fiberoptic Insight scanners, 95IRS2, 95UVS2, 95IRS2E, 95UVS2E, 61-6960, 61-7080 CU-102 FS950W Software for Insight Scanner
IC-4851 IC485 Optically isolated RS232/RS485 converter - OBSOLETE 133-656 Installation Instructions for 129-164 cable connector
133-692 Adapter Kit Installation Instructions for 129-181-1 & 129-181-2 Detector Electronics Fiber Optics to InSight Scanner 133-711 Installation of IR Filter and O-Ring Retainer for use with Insight 95IRS2-2 Flame Scanners
UC-4851 UC485 Optically isolated USB to RS422/RS485 converter 133-720 InSight Fiber Optic Flame Scanners Errata Sheet
133-752 60-2721-x replacement electronics assembly for InSight I CEX scanner 133-754 Installation instructions p/n 129-193 adapter kit
133-732 Installation instructions EP178 / EP378 with EDC1 / EDC2 using Phoenix WR or InSight with 59-497-020WR 133-733 Installation instructions MicroM MEP237 with MEDC2 using Phoenix WR or InSight with 59-497-020WR
133-769
new 59-547-XXX PLTC-ER cable 133-768 61-7379 cable adapter to upgrade an existing 45FS1 / 45UVFS1 flame scanner to an InSight 1

Service Online
Phone online