Date:2017-10-27 Hits:5570
Valve actuators mount directly onto flanged or threaded globe valves or unitary valves for control in HVAC systems.
Valve/Modulating Actuator Combination
VC7936MK6400/U
3-way 3/4 in fNPT VC Valve Assembly
Overview
The VC7936 Fail Safe Modulating Control Valve provides proportional control of hot or chilled water in commercial heating and cooling applications, such as unit ventilators. On a power failure, this patented actuator design drives the valve to the fail safe position, either fully open or closed, according to the installer’s wiring connections. The VC7936 uses a microprocessor-controlled, low voltage stepper motor with a supercapacitor-based power supply capable of storing enough power to drive the valve to its fail safe position when 24V power is removed from the actuator. DIP switches are used to select actuator response time, flow characterization, motor timing, and control signal.
Features
2-way straight-through or 3-way mixing/diverting body configurations
Corrosion resistant, engineered plastic actuator housing
60 psid close-off on all models
Fast acting 2-position actuator with soft close technology
Position indicator/manual override lever standard
Replaceable cartridge rebuilds valve to factory specifications without removing valve body from piping
300 psi operating pressure
Combination position indicator/manual flush-and-fill manual lever on all actuators
Product Specifications
Maximum Safe Operating Pressure (psi)300 psiMaximum Safe Operating Pressure (kPa)2068 kappa (20 Bar)Commentscharacterized cartridge for use with non-fail safe floating and modulating actuatorsApprovals, Canadian Standards AssociationCSA CertifiedTimingWhen used with VC series Actuator--Installer-selectable 60 or 120 secondsAmbient Temperature Range (F)32 F to 150 FAmbient Temperature Range (C)0 C to 65 CConnection TypeFemale NPTBody PatternThree-way A-AB-BPipe Size (inch)3/4 in.Pipe Size (DN)DN20Fluid Temperature (C)1 C to 95 CFluid Temperature (F)34 F to 203 FMaximum Differential Pressure Ratings (Close-off) (psi)60 psiMaximum Differential Pressure Ratings (Close-off) (kPa)414 kPa (4 bar)Capacity (Cv)4.2 CvCapacity (Kv)3.6 kvsValve ActionStem up to close A portValve TypeCartridge Cage ValveControlled FluidChilled or hot water with up to 60% GlycolMaterials (Body)BronzeMaterials (Seat)EPDM O-ring seals on Noryl pistonMaterials (Stem)Stainless SteelMaterials (Cartridge)Ryton™, Noryl™ engineering plasticFlow CharacteristicModified Equal PercentActuationModulating/Floating/PWM fail-safeStem Travel (in.)0.4 in.Stem Travel (mm)10 mmMaterials (Packing)EPDM rubber
VC6936NE6100/U
3-way 1-1/4 in Sweat VC Valve Assembly
Overview
The VC6936 Fail Safe Floating Control Valve provides proportional control of hot or chilled water in commercial heating and cooling applications, such as unit ventilators. On a power failure, this patented actuator design drives the valve to the fail safe position, either fully open or closed according to the installer’s wiring connections. The VC6936 uses a microprocessor-controlled, low voltage stepper motor with a supercapacitor-based power supply capable of storing enough power to drive the valve to its fail safe position when 24V power is removed from the actuator. The VC hydronic valve consists of a valve body and replaceable characterized cartridge assembly. When used with a Honeywell VC6900 or VC7900-series actuator, the valve provides proportional flow control. Three-way bodies may use cam-operated cartridge travel to resist water hammer. Limit switches prevent motor overrun.
Product Specifications
Maximum Safe Operating Pressure (psi)300 psiMaximum Safe Operating Pressure (kPa)2068 kappa (20 Bar)IncludesCartridge changing toolCommentscharacterized cartridge for use with non-fail safe floating and modulating actuatorsApprovals, Canadian Standards AssociationCSA CertifiedTimingWhen used with VC series Actuator--2 minutesAmbient Temperature Range (F)32 F to 150 FAmbient Temperature Range (C)0 C to 65 CConnection TypeSweatBody PatternThree-way A-AB-BPipe Size (inch)1 1/4 in.Pipe Size (DN)DN32Fluid Temperature (C)1 C to 95 CFluid Temperature (F)34 F to 203 FMaximum Differential Pressure Ratings (Close-off) (psi)60 psiMaximum Differential Pressure Ratings (Close-off) (kPa)414 kPa (4 bar)Capacity (Cv)9 CvCapacity (Kv)7.8 kvsValve ActionStem up to close A portValve TypeCartridge Cage ValveControlled FluidChilled or hot water with up to 60% GlycolMaterials (Body)BronzeMaterials (Seat)EPDM O-ring seals on Noryl pistonMaterials (Stem)Stainless SteelMaterials (Cartridge)Ryton™, Noryl™ engineering plasticFlow CharacteristicLinearActuationFloating (24V SP3T) fail-safeStem Travel (in.)0.4 in.Stem Travel (mm)10 mmMaterials (Packing)EPDM rubber
VC6936ND6100/U
3-way 1-1/4 in fNPT VC Valve Assembly
Overview
The VC6936 Fail Safe Floating Control Valve provides proportional control of hot or chilled water in commercial heating and cooling applications, such as unit ventilators. On a power failure, this patented actuator design drives the valve to the fail safe position, either fully open or closed according to the installer’s wiring connections. The VC6936 uses a microprocessor-controlled, low voltage stepper motor with a supercapacitor-based power supply capable of storing enough power to drive the valve to its fail safe position when 24V power is removed from the actuator. The VC hydronic valve consists of a valve body and replaceable characterized cartridge assembly. When used with a Honeywell VC6900 or VC7900-series actuator, the valve provides proportional flow control. Three-way bodies may use cam-operated cartridge travel to resist water hammer. Limit switches prevent motor overrun.
Product Specifications
Maximum Safe Operating Pressure (psi)300 psiMaximum Safe Operating Pressure (kPa)2068 kappa (20 Bar)Commentscharacterized cartridge for use with non-fail safe floating and modulating actuatorsApprovals, Canadian Standards AssociationCSA CertifiedTimingWhen used with VC series Actuator--2 minutesAmbient Temperature Range (F)32 F to 150 FAmbient Temperature Range (C)0 C to 65 CConnection TypeFemale NPTBody PatternThree-way A-AB-BPipe Size (inch)1 1/4 in.Pipe Size (DN)DN32Fluid Temperature (C)1 C to 95 CFluid Temperature (F)34 F to 203 FMaximum Differential Pressure Ratings (Close-off) (psi)60 psiMaximum Differential Pressure Ratings (Close-off) (kPa)414 kPa (4 bar)Capacity (Cv)9 CvCapacity (Kv)7.8 kvsValve ActionStem up to close A portValve TypeCartridge Cage ValveControlled FluidChilled or hot water with up to 60% GlycolMaterials (Body)BronzeMaterials (Seat)EPDM O-ring seals on Noryl pistonMaterials (Stem)Stainless SteelMaterials (Cartridge)Ryton™, Noryl™ engineering plasticFlow CharacteristicLinearActuationFloating (24V SP3T) fail-safeStem Travel (in.)0.4 in.Stem Travel (mm)10 mmMaterials (Packing)EPDM rubber
ML4702
Honeywell ML4115 direct coupled actuators (DCA) for damper control accepts an on/off signal from a single-pole, single-throw (SPST) controller. Operates reliably in smoke control systems requiring UL555S ratings up to 350F.
ML4702F1009/B
Fast-Acting, Two-Position Actuator - 20 lb-in, Spring Return CW, 230 Vac ±-10%
Overview
Honeywell ML4702 fast-acting, two-position spring return, double coupled actuators feature on/off damper control. Reliably operates in smoke control systems requiring UL 555S ratings up to 350F.
Features
20 lb-in. (22Nm) minimum driving torque at 350F (176C)
Integral spring return
Stainless steel internal spring features fifteen-second spring return timing
Ninety-five degree angle of rotation
No audible noise and no special cycling during holding
Actuator holds rated torque at reduced power level
Die-cast aluminum housing allows flush mounting to damper
Integral junction box with one conduit opening eliminates separate wiring box
Models available for 24, 120 and 230 Vac
Product Specifications
ApplicationFire and SmokeDimensions (in.)7.5 in high x 5.13 in wide x 3.32 in deepDimensions (mm)192 mm high x 129 mm wide x 84 mm deepWeight (lb)6 lbWeight (kg)2.72 kgMaterialsAluminum housingCommentsIntegral junction box with three 7/8 in. conduit openings (fittings not included)MountingDirect CoupledFrequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.UL873, Plenum RatedCustomer SpecialRuskinElectrical ConnectionsAppliance cableOperating Humidity Range (% RH)5 to 95% RH, non-condensingSupply Voltage230 Vac ±10%Power ConsumptionDriving-- 0.13A, 18W, Holding-- 0.10A, 11WShipping and Storage Temperature Range (F)-40 F to 140 FShipping and Storage Temperature Range (C)-40 C to +60 CApprovals, CE89/336/ECC, 73/23/EECApprovals, Canadian Underwriters Laboratories Inc.cUL C22.2 No. 24-93Ambient Temperature Range (F)0 F to +130 FAmbient Temperature Range (C)-18 C to +55 CApprovals, C-TickN314Environmental, Electrical or Ingress Protection RatingNEMA 1Internal Auxiliary Switch0Maximum Noise RatingDriving (dB(A) @ 1m)-- 65; Holding (dB(A) @ 1m)-- 20 (no audible noise)Stroke95 ±3 degreesShaft Dimensions (in.)3/8 to 1/2 in. square or roundActuator TypeDamperControl SignalTwo position; SPSTFail Safe ModeSpring ReturnTorque Rating (lb-in.)20 lb-in.Torque Rating (Nm)2.3 NmSpring Return Torque/Force (lb-in., lbf)20 lb-in.Spring Return Torque/Force (Nm, N)2.3 NmAdditional Torque Ratings (lb-in.)Maximum Stall-- 150 lb-in.; Minimum Driving at 350 F-- 20 lb-in.Additional Torque Ratings (Nm)Maximum Stall-- 17 Nm; Minimum Driving at 175 C-- 2.3 NmExternal Auxiliary Switches AvailableYes, 32003532-003Timing, NominalDriving @ 60 Hz-- 18 sec, 25 sec maximumSpring Return TimingMaximum-- 15 secShaft Adapter TypeAluminum Hub, two set screwsShaft Dimensions (mm)10 to 13 mm square/roundSpring Return DirectionCWElectrical Connections (in.)39 in.Electrical Connections (mm)1 m
M6435/M7435
Cartridge globe valve spring return actuators are small electric actuators for individual room control that provide floating or modulating control of V5852, V5862 two-way or V5853, V5863 three-way valves.
M6435A1004
Spring Ret Float Cart.Globe Vlv Actuator
Overview
Cartridge Globe Valve Spring Return Actuators are small electric actuators for individual room control that provide floating or modulating control of V5852, V5862 two-way or V5853, V5863 three-way valves.
Features
Stem actuator retracts up on power failure. Fail safe mode depends on valve seat rest position.
Suitable for Excel/IRC system or other controllers providing specified signals.
Magnetic coupling for torque limitation independent of voltage supply and self-adjustment of the close-off port.
No mounting tools required.
Compact size allows installation in limited space of fan coil units, induction units, and small reheaters or recoolers.
Visual position indication (red disk).
Product Specifications
ApplicationHVACDimensions (in.)3 3/16 in. high x 4 1/4 in. wide x 5 in. deepDimensions (mm)81 mm high x 108 mm wide x 126 mm deepIncludes1/2 in. conduit hubUsed With1/2 inch and 3/4 inch V58XX Globe ValvesWeight (lb)1.1 lbWeight (kg)0.5 kgMaterialsLow Maintenance Plastic HousingItem TypeProductMountingThreads onto V58XX valve bonnetFrequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.Flammability Rating UL94V-5VElectrical ConnectionsScrew terminalsOperating Humidity Range (% RH)5 to 95% RHSupply Voltage24 Vac +20%, -15%Power ConsumptionDriving-- 10 VAShipping and Storage Temperature Range (F)-40 F to +158 FShipping and Storage Temperature Range (C)-40 C to +70 CAmbient Temperature Range (F)32 F to 122 FAmbient Temperature Range (C)0 C to 50 CEnvironmental, Electrical or Ingress Protection RatingIP54,Class I Insulation (24 Vac)Internal Auxiliary Switch0Fluid Temperature (C)130 C MaximumFluid Temperature (F)266 F MaximumActuator TypeValveControl SignalSPDT; Two position; FloatingFail Safe Mode(Normally open for 1/2 in. and 3/4 in. V5852 and V5862. Normally closed for all other V58XX valves.); Spring Return, operator retracts upTorque Rating (lb-in.)40.5 lbfTorque Rating (Nm)180 NSpring Return Torque/Force (lb-in., lbf)40.5 lbfSpring Return Torque/Force (Nm, N)180 NSwitchesNoStroke (in.)1/4 in.Stroke (mm)6 mmCableThreaded conduit connectorTiming, NominalDriving @ 60 Hz-- 50 secSpring Return TimingNominal-- 10 secFeedbackNoManual operationNone (use valve dust cap)Spring Return DirectionStem up
M6435A3000
Spring Ret Float Cart.Globe Vlv Actuator
Overview
Cartridge Globe Valve Spring Return Actuators are small electric actuators for individual room control that provide floating or modulating control of V5852, V5862 two-way or V5853, V5863 three-way valves.
Features
Stem actuator retracts up on power failure. Fail safe mode depends on valve seat rest position.
Suitable for Excel/IRC system or other controllers providing specified signals.
Magnetic coupling for torque limitation independent of voltage supply and self-adjustment of the close-off port.
No mounting tools required.
Compact size allows installation in limited space of fan coil units, induction units, and small reheaters or recoolers.
Visual position indication (red disk).
Product Specifications
ApplicationHVACDimensions (in.)3 3/16 in. high x 4 1/4 in. wide x 5 in. deepDimensions (mm)81 mm high x 108 mm wide x 126 mm deepIncludes1/2 in. conduit hubUsed With1 inch to 1-1/2 inch V58XX Globe ValvesWeight (lb)1.1 lbWeight (kg)0.5 kgMaterialsLow Maintenance Plastic HousingCommentsHigh force for metal-seated valvesItem TypeProductMountingThreads onto V58XX valve bonnetFrequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.Flammability Rating UL94V-5VElectrical ConnectionsScrew terminalsOperating Humidity Range (% RH)5 to 95% RHSupply Voltage24 Vac +20%, -15%Power ConsumptionDriving-- 10 VAShipping and Storage Temperature Range (F)-40 F to +158 FShipping and Storage Temperature Range (C)-40 C to +70 CAmbient Temperature Range (F)32 F to 122 FAmbient Temperature Range (C)0 C to 50 CEnvironmental, Electrical or Ingress Protection RatingIP54,Class I Insulation (24 Vac)Internal Auxiliary Switch0Fluid Temperature (C)130 C MaximumFluid Temperature (F)266 F MaximumActuator TypeValveControl SignalSPDT; Two position; FloatingFail Safe Mode(Normally open for 1/2 in. and 3/4 in. V5852 and V5862. Normally closed for all other V58XX valves.); Spring Return, operator retracts upTorque Rating (lb-in.)90 lbfTorque Rating (Nm)400 NSpring Return Torque/Force (lb-in., lbf)90 lbfSpring Return Torque/Force (Nm, N)400 NSwitchesNoStroke (in.)1/4 in.Stroke (mm)6 mmCableThreaded conduit connectorTiming, NominalDriving @ 60 Hz-- 50 secSpring Return TimingNominal-- 10 secFeedbackNoManual operationNone (use valve dust cap)Spring Return DirectionStem up
M7435F1001
Spring Ret Mod. Cart.Globe Vlv Actuator
Overview
Cartridge Globe Valve Spring Return Actuators are small electric actuators for individual room control that provide floating or modulating control of V5852, V5862 two-way or V5853, V5863 three-way valves.
Features
Stem actuator retracts up on power failure. Fail safe mode depends on valve seat rest position.
Suitable for Excel/IRC system or other controllers providing specified signals.
Magnetic coupling for torque limitation independent of voltage supply and self-adjustment of the close-off port.
No mounting tools required.
Compact size allows installation in limited space of fan coil units, induction units, and small reheaters or recoolers.
Visual position indication (red disk).
Product Specifications
ApplicationHVACDimensions (in.)3 3/16 in. high x 4 1/4 in. wide x 5 in. deepDimensions (mm)81 mm high x 108 mm wide x 126 mm deepIncludes1/2 in. conduit hubUsed With1/2 inch and 3/4 inch V58XX Globe ValvesWeight (lb)1.1 lbWeight (kg)0.5 kgMaterialsLow Maintenance Plastic HousingCommentsDirect/Reverse Acting SwitchItem TypeProductMountingThreads onto V58XX valve bonnetFrequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.Flammability Rating UL94V-5VElectrical ConnectionsScrew terminalsOperating Humidity Range (% RH)5 to 95% RHSupply Voltage24 Vac +20%, -15%Power ConsumptionDriving-- 5 VAShipping and Storage Temperature Range (F)-40 F to +158 FShipping and Storage Temperature Range (C)-40 C to +70 CAmbient Temperature Range (F)32 F to 122 FAmbient Temperature Range (C)0 C to 50 CEnvironmental, Electrical or Ingress Protection RatingIP54,Class I Insulation (24 Vac)Internal Auxiliary Switch0Fluid Temperature (C)130 C MaximumFluid Temperature (F)266 F MaximumActuator TypeValveControl Signal0 to 10 Vdc; 2 to 10 VdcFail Safe Mode(Normally open for 1/2 in. and 3/4 in. V5852 and V5862. Normally closed for all other V58XX valves.); Spring Return, operator retracts upTorque Rating (lb-in.)40.5 lbfTorque Rating (Nm)180 NSpring Return Torque/Force (lb-in., lbf)40.5 lbfSpring Return Torque/Force (Nm, N)180 NSwitchesNoStroke (in.)1/4 in.Stroke (mm)6 mmCableThreaded conduit connectorTiming, NominalDriving @ 60 Hz-- 50 secSpring Return TimingNominal-- 10 secFeedbackNoManual operationNone (use valve dust cap)Spring Return DirectionStem upInput Impedance100K ohm
M7435F3007
Spring Ret Mod. Cart.Globe Vlv Actuator
Overview
Cartridge Globe Valve Spring Return Actuators are small electric actuators for individual room control that provide floating or modulating control of V5852, V5862 two-way or V5853, V5863 three-way valves.
Features
Stem actuator retracts up on power failure. Fail safe mode depends on valve seat rest position.
Suitable for Excel/IRC system or other controllers providing specified signals.
Magnetic coupling for torque limitation independent of voltage supply and self-adjustment of the close-off port.
No mounting tools required.
Compact size allows installation in limited space of fan coil units, induction units, and small reheaters or recoolers.
Visual position indication (red disk).
Product Specifications
ApplicationHVACDimensions (in.)3 3/16 in. high x 4 1/4 in. wide x 5 in. deepDimensions (mm)81 mm high x 108 mm wide x 126 mm deepIncludes1/2 in. conduit hubUsed With1 inch to 1-1/2 inch V58XX Globe ValvesWeight (lb)1.1 lbWeight (kg)0.5 kgMaterialsLow Maintenance Plastic HousingCommentsDirect/Reverse Acting Switch; High force for metal-seated valvesItem TypeProductMountingThreads onto V58XX valve bonnetFrequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.Flammability Rating UL94V-5VElectrical ConnectionsScrew terminalsOperating Humidity Range (% RH)5 to 95% RHSupply Voltage24 Vac +20%, -15%Power ConsumptionDriving-- 5 VAShipping and Storage Temperature Range (F)-40 F to +158 FShipping and Storage Temperature Range (C)-40 C to +70 CAmbient Temperature Range (F)32 F to 122 FAmbient Temperature Range (C)0 C to 50 CEnvironmental, Electrical or Ingress Protection RatingIP54,Class I Insulation (24 Vac)Internal Auxiliary Switch0Fluid Temperature (C)130 C MaximumFluid Temperature (F)266 F MaximumActuator TypeValveControl Signal0 to 10 Vdc; 2 to 10 VdcFail Safe Mode(Normally open for 1/2 in. and 3/4 in. V5852 and V5862. Normally closed for all other V58XX valves.); Spring Return, operator retracts upTorque Rating (lb-in.)90 lbfTorque Rating (Nm)400 NSpring Return Torque/Force (lb-in., lbf)90 lbfSpring Return Torque/Force (Nm, N)400 NSwitchesNoStroke (in.)1/4 in.Stroke (mm)6 mmCableThreaded conduit connectorTiming, NominalDriving @ 60 Hz-- 50 secSpring Return TimingNominal-- 10 secFeedbackNoManual operationNone (use valve dust cap)Spring Return DirectionStem upInput Impedance100K ohm
Fan Coil Valve Actuators
Humidity resistant fan coil valve actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
VU443A1008/B
Valve Actuator - 120V 60hz 2W - 6" Leads
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationHVACDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NC VU valve body (VU53)MaterialsStainless Case, Aluminum CoverCommentsFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsItem TypeProductFrequency60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage120VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)22 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 4 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU443A1008/U
Valve Actuator - 120V 60hz 2W - 6" Leads
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NC VU valve body (VU53)MaterialsStainless Steel Case, Aluminum CoverItem TypeProductFrequency60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage120VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)22 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 4 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU443A1057/U
Valve Actuator - 277V 60hz 2W- 18" Leads
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NC VU valve body (VU53)MaterialsStainless Steel Case, Aluminum CoverItem TypeProductFrequency60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage277VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)22 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 4 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)18 in.Electrical Connections (mm)0.5 m
VU443A1115/B
Valve Actuator - 230V 50hz 2W - 6" Leads
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationHVACDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NC VU valve body (VU53)MaterialsStainless Case, Aluminum CoverCommentsFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsItem TypeProductFrequency50 Hz; 60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage230VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)22 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 4 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU443A1115/U
Valve Actuator - 230V 50hz 2W - 6" Leads
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NC VU valve body (VU53)MaterialsStainless Steel Case, Aluminum CoverItem TypeProductFrequency50 Hz; 60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage230VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)22 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 4 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU444A1007/B
Valve Actuator - 120V 60hz 2W - 6" Leads
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationHVACDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NO (VU52) or 3-way VU valve body (VU54)MaterialsStainless Case, Aluminum CoverCommentsFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsItem TypeProductFrequency60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage120VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)45 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 6 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU444A1007/U
Valve Actuator - 120V 60hz 2W - 6" Leads
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NO (VU52) or 3-way VU valve body (VU54)MaterialsStainless Steel Case, Aluminum CoverItem TypeProductFrequency60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage120VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)45 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 6 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU444A1106/B
Valve Actuator - 230V 50hz 2W- 6" Leads
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationHVACDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NO (VU52) or 3-way VU valve body (VU54)MaterialsStainless Case, Aluminum CoverCommentsFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsItem TypeProductFrequency50 Hz; 60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage230VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)45 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 6 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU444A1106/U
Valve Actuator - 230V 50hz 2W - 6" Leads
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NO (VU52) or 3-way VU valve body (VU54)MaterialsStainless Steel Case, Aluminum CoverItem TypeProductFrequency50 Hz; 60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage230VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)45 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 6 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU444A1155/U
Two-position actuator for valve bodies with 120V, 60Hz
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NO (VU52) or 3-way VU valve body (VU54)MaterialsStainless Steel case, Aluminum cover, Ni-plated motorCommentsNickel plated motor for added humidity resistance; For controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsItem TypeProductFrequency60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage120VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)45 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 6 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU843A1004/B
Valve Actuator - 24V 50/60hz 2W- 6" Lead
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationHVACDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NC VU valve body (VU53)MaterialsStainless Case, Aluminum CoverCommentsFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsItem TypeProductFrequency50 Hz; 60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage24VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)22 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 4 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU843A1004/U
Valve Actuator - 24V 50/60hz 2W- 6" Lead
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NC VU valve body (VU53)MaterialsStainless Steel Case, Aluminum CoverItem TypeProductFrequency50 Hz; 60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage24VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)22 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 4 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU844A1003/B
Valve Actuator - 24V 50/60hz 2W -6" Lead
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationHVACDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NO (VU52) or 3-way VU valve body (VU54)MaterialsStainless Case, Aluminum CoverCommentsFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsItem TypeProductFrequency50 Hz; 60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage24VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)45 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 6 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU844A1003/U
Valve Actuator - 24V 50/60hz 2W -6" Lead
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NO (VU52) or 3-way VU valve body (VU54)MaterialsStainless Steel Case, Aluminum CoverItem TypeProductFrequency50 Hz; 60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage24VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)45 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 6 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
VU844A1060/U
Two-position actuator for valve bodies with 24V, 50/60Hz
Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
Compact construction for easy installation.
Fits under the cover of most baseboard convectors with actuator fitted to valve body.
One-button, quick release. Secure 3-point, metal latch to valve body.
Spring return operation.
Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
Line or low voltage, rust-resistant motors.
Manual opener for installation and valve operation on power failure.
Valve returns to automatic position when power is restored.
Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
Slotted conduit hole for faster wiring.
Product Specifications
ApplicationFor controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsDimensions (in.)2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wideDimensions (mm)62 mm high, 88 mm wide, 60 mm deepUsed With2-way NO (VU52) or 3-way VU valve body (VU54)MaterialsStainless Steel case, Aluminum cover, Ni-plated motorCommentsNickel plated motor for added humidity resistance; For controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectorsItem TypeProductFrequency50 Hz; 60 HzApprovals, Canadian Standards AssociationCertified C/US File No. LR1322Electrical ConnectionsLeadsSupply Voltage24VPower ConsumptionDriving-- 6 WattsAmbient Temperature Range (F)34 F to 125 F ambient at 200 F FluidAmbient Temperature Range (C)1 C to 52 C ambient at 93 C FluidInternal Auxiliary Switch0Fluid Temperature (C)94 CFluid Temperature (F)200 FActuator TypeValveControl SignalTwo position; SPSTFail Safe ModeSpring ReturnStroke (in.)45 deg.Timing, NominalDriving @ 60 Hz (sec)-- 15 sec maximumSpring Return TimingNominal-- 6 secMaximum Differential Pressure Ratings (Close-off) (psi)Depends on Cv rating of valveMaximum Differential Pressure Ratings (Close-off) (kPa)Depends on Cv rating of valveManual operationLeverElectrical Connections (in.)6 in.Electrical Connections (mm)0.15 m
ML6420/ML7420
Non-spring return electric linear valve actuators have floating or modulating control and operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications.
ML6420A3049
Non-spring return direct-coupled, linear-stroke, 135 lbf valve actuator
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
Product Specifications
ApplicationHVACDimensions (in.)9 9/16 in. high x 5 5/16 in. wide x 6 5/16 in. deepDimensions (mm)242 mm high x 135 mm wide x 161 mm deepIncludes1/2 in. conduit hub; 1/2 in. flexible conduit adapterWeight (lb)2.9 lbWeight (kg)1.3 kgMaterialsABS-FR Plastic, aluminum yokeItem TypeProductMountingDirectly on V5011/V5013 Globe Valves and VGF Flanged Globe Valves (3/4" or 20mm stroke)Frequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.Flammability Rating UL94V-5VApprovals, Canadian Standards AssociationCertifiedElectrical ConnectionsScrew terminalsOperating Humidity Range (% RH)5 to 95% RHSupply Voltage24 Vac ±15%Power ConsumptionDriving-- 6 VAShipping and Storage Temperature Range (F)-40 F to +158 FShipping and Storage Temperature Range (C)-40 C to +70 CApprovals, CEListedAmbient Temperature Range (F)14 F to 122 FAmbient Temperature Range (C)-10 C to +50 CEnvironmental, Electrical or Ingress Protection RatingIP54,Class I Insulation (24 Vac)Internal Auxiliary Switch0Fluid Temperature (C)150 C MaximumFluid Temperature (F)300 F MaximumActuator TypeValveControl SignalSPDT; Two position; FloatingFail Safe ModeStays in placeTorque Rating (lb-in.)135 lbfTorque Rating (Nm)600 NSwitchesYesStroke (in.)3/4 in.Stroke (mm)20 mmCableConduit connector and one knockout on actuator caseTiming, NominalDriving @ 60 Hz-- 60 secManual operationKnob
ML6420A3056
Non-spring return direct-coupled, linear-stroke, 135 lbf valve actuator
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
Product Specifications
ApplicationHVACDimensions (in.)9 9/16 in. high x 5 5/16 in. wide x 6 5/16 in. deepDimensions (mm)242 mm high x 135 mm wide x 161 mm deepIncludes1/2 in. conduit hub; 1/2 in. flexible conduit adapterWeight (lb)2.9 lbWeight (kg)1.3 kgMaterialsABS-FR Plastic, aluminum yokeItem TypeProductMountingDirectly on V5011/V5013 Globe Valves and VGF Flanged Globe Valves (3/4" or 20mm stroke)Frequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.Flammability Rating UL94V-5VApprovals, Canadian Standards AssociationCertifiedElectrical ConnectionsScrew terminalsOperating Humidity Range (% RH)5 to 95% RHSupply Voltage24 Vac ±15%Power ConsumptionDriving-- 6 VAShipping and Storage Temperature Range (F)-40 F to +158 FShipping and Storage Temperature Range (C)-40 C to +70 CApprovals, CEListedAmbient Temperature Range (F)14 F to 122 FAmbient Temperature Range (C)-10 C to +50 CEnvironmental, Electrical or Ingress Protection RatingIP54,Class I Insulation (24 Vac)Internal Auxiliary Switch0Fluid Temperature (C)150 C MaximumFluid Temperature (F)300 F MaximumActuator TypeValveControl SignalSPDT; Two position; FloatingFail Safe ModeStays in placeTorque Rating (lb-in.)135 lbfTorque Rating (Nm)600 NSwitchesYesStroke (in.)3/4 in.Stroke (mm)20 mmCableConduit connector and one knockout on actuator caseTiming, NominalDriving @ 60 Hz-- 30 secManual operationKnob
Creval Non-spring return on/off actuator
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
Product Specifications
ApplicationHVACIncludes1/2 in. conduit hub; 1/2 in. flexible conduit adapterMountingDirectly on V5011/V5013 Globe Valves and VGF Flanged Globe Valves (3/4" or 20mm stroke)Frequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.Flammability Rating UL94V-5VApprovals, Canadian Standards AssociationCertifiedElectrical ConnectionsScrew terminalsShipping and Storage Temperature Range (F)-40 F to +158 FShipping and Storage Temperature Range (C)-40 C to +70 CApprovals, CEListedAmbient Temperature Range (F)14 F to 122 FAmbient Temperature Range (C)-10 C to +50 CEnvironmental, Electrical or Ingress Protection RatingClass I Insulation (24 Vac),IP54Internal Auxiliary Switch0Fluid Temperature (C)150 C MaximumFluid Temperature (F)300 F MaximumActuator TypeValveControl SignalSPDT; Two position; FloatingFail Safe ModeStays in placeTorque Rating (lb-in.)135 lbfTorque Rating (Nm)600 NStroke (in.)3/4 in.Stroke (mm)20 mmCableConduit connector and one knockout on actuator caseManual operationKnob
ML7420A3055
Non-spring return direct-coupled Valve Actuator with 135 lbf rated force
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
Product Specifications
ApplicationHVACDimensions (in.)9 9/16 in. high x 5 5/16 in. wide x 6 5/16 in. deepDimensions (mm)242 mm high x 135 mm wide x 161 mm deepIncludes1/2 in. flexible conduit adapter; 1/2 in. conduit hubWeight (lb)2.9 lbWeight (kg)1.3 kgMaterialsABS-FR Plastic, aluminum yokeItem TypeProductMountingDirectly on V5011/V5013 Globe Valves and VGF Flanged Globe Valves (3/4" or 20mm stroke)Frequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.Flammability Rating UL94V-5VApprovals, Canadian Standards AssociationCertifiedElectrical ConnectionsScrew terminalsOperating Humidity Range (% RH)5 to 95% RHSupply Voltage24 Vac ±15%Power ConsumptionDriving-- 7 VAShipping and Storage Temperature Range (F)-40 F to +158 FShipping and Storage Temperature Range (C)-40 C to +70 CApprovals, CEListedAmbient Temperature Range (F)14 F to 122 FAmbient Temperature Range (C)-10 C to +50 CEnvironmental, Electrical or Ingress Protection RatingClass I Insulation (24 Vac),IP54Internal Auxiliary Switch0Fluid Temperature (C)150 C MaximumFluid Temperature (F)300 F MaximumActuator TypeValveControl Signal0 to 10 Vdc; 2 to 10 VdcFail Safe ModeStays in placeTorque Rating (lb-in.)135 lbfTorque Rating (Nm)600 NSwitchesYesStroke (in.)3/4 in.Stroke (mm)20 mmCableConduit connector and one knockout on actuator caseTiming, NominalDriving @ 60 Hz-- 60 secFeedback2-10 VdcManual operationKnobInput Impedance1K ohm
ML7420A3063
Non-spring return direct-coupled Valve Actuator with 135 lbf rated force
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
Product Specifications
ApplicationHVACDimensions (in.)9 9/16 in. high x 5 5/16 in. wide x 6 5/16 in. deepDimensions (mm)242 mm high x 135 mm wide x 161 mm deepIncludes1/2 in. conduit hub; 1/2 in. flexible conduit adapterWeight (lb)2.9 lbWeight (kg)1.3 kgMaterialsABS-FR Plastic, aluminum yokeItem TypeProductMountingDirectly on V5011/V5013 Globe Valves and VGF Flanged Globe Valves (3/4" or 20mm stroke)Frequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.Flammability Rating UL94V-5VApprovals, Canadian Standards AssociationCertifiedElectrical ConnectionsScrew terminalsOperating Humidity Range (% RH)5 to 95% RHSupply Voltage24 Vac ±15%Power ConsumptionDriving-- 7 VAShipping and Storage Temperature Range (F)-40 F to +158 FShipping and Storage Temperature Range (C)-40 C to +70 CApprovals, CEListedAmbient Temperature Range (F)14 F to 122 FAmbient Temperature Range (C)-10 C to +50 CEnvironmental, Electrical or Ingress Protection RatingIP54,Class I Insulation (24 Vac)Internal Auxiliary Switch0Fluid Temperature (C)150 C MaximumFluid Temperature (F)300 F MaximumActuator TypeValveControl Signal0 to 10 Vdc; 2 to 10 VdcFail Safe ModeStays in placeTorque Rating (lb-in.)135 lbfTorque Rating (Nm)600 NSwitchesYesStroke (in.)3/4 in.Stroke (mm)20 mmCableConduit connector and one knockout on actuator caseTiming, NominalDriving @ 60 Hz-- 30 secFeedback2-10 VdcManual operationKnobInput Impedance1K ohm
ACTUATOR 600N 24V 50/60HZ
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
ML6420A3015
ACTUATOR 600N 230V 50/60HZ
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
ML6420A3023
ACTUATOR 600N 24VAC 30SEC NSR
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
ACTUATOR 600N 230VAC 30SEC
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
ML7300A1004
SMARTFIT ACTUATOR - SPARES AND TRADE
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
ML7420A6009
CREVAL MOD, 60S ( DRAWING 50006745 )-ML7
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
ACTUATOR 600N 24VAC 30SEC PNSR
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
CREVAL MOD, 60S, LC ( DRAWING 50007339
Overview
The Non-Spring Return Electric Linear Valve Actuators have floating or modulating control. These actuators operate standard Honeywell valves in heating, ventilating, and air conditioning (HVAC) applications. Floating control actuators are used with controllers that provide a switched or floating single-pole double-throw (SPDT) output. Modulating control actuators are used with controllers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
Features
Easy and quick installation on valves with 1 3/8 in. bonnet and 3/4 in. stroke
No separate linkage required
Conduit connector standard
No adjustments required on linkage.
Accurate valve positioning
Low power consumption
High close-off ratings
Force limiting end switches
Manual operator
Synchronous motor
Maintenance free
ML7420 has an internal selector plug that can be used to reverse the direction of action.
Direct Coupled Valve Actuator Accessories and Parts
Auxiliary Potentiometers, switches, adapter kits and more parts and accessories for direct coupled valve actuators.
VC Series Two-position Actuators
Control central heating and/or cooling systems, fan coil systems, radiators and convectors. Depending on the model selected, the actuator can be controlled by either a low or line voltage SPST or SPDT controller such as a room thermostat.
VC Series Floating/Modulating Actuators
Control central heating and cooling, fan coil systems, radiators and convectors. Depending on the model, the actuator can be controlled by a low voltage SPST or SPDT switch, pulse-width modulated 24 Vac signal, or floating input, modulating controller.
VC Series Fail Safe Floating/Modulating Actuators
Control central heating and/or cooling systems, fan coil systems, radiators and convectors. Depending on the model selected, the actuator can be controlled by either a low or line voltage SPST or SPDT or floating or modulating controller.
MVN
MVN rotary valve actuators for use with control ball valves and pressure independent control valves. Reduce labor costs associated with mechanical and electrical installation, commissioning and service. Innovative design makes assembly easy, saving you time and money.
MVNACTUATOR
MVN rotary valve actuator
Automatic Cross Reference Tool and Price List
Tags can be added to this product in your Shopping Cart or Product List.
Overview
The new MVN rotary valve actuator for use with control ball valves and pressure regulated control valves reduces labor costs associated with mechanical and electrical installation, commissioning and service. This innovative design makes assembly easy, saving you time and money. MVN actuators and control valves can be ordered separately, or as assemblies. The Fast Track tool is available to help you select the right valve and actuator combinations for the job. All valve, actuator and assemblies are orderable through the Fast Track tool.
Features
Non-spring Return
Floating and modulating
Space saving, click-on installation – no tool required
Extendable position indicator for easy commissioning
Available with or without cable
Compatible with control ball valves from 1/2 to 1-1/4 inches.
Actuator can be mounted on the valve in any of four positions.
Product Specifications
MaterialsPlenum rated plastic housingCommentsDesign Life (at Rated Voltage): 60,000 cycles; 1 cycle = 0°…90°…0°Item TypeProductMountingClick-on installation – no tool requiredFrequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.UL/cUL; UL60730Operating Humidity Range (% RH)5 to 95% RH, noncondensingSupply Voltage24 Vac +20%, -15%, 24 VdcPower Consumption5 VA- Modulating; 1.5 VA - Floating; 6 VA - Fast Acting SPDTShipping and Storage Temperature Range (F)-40 F to 176 F Shipping and Storage Temperature Range (C)-40 C to 80 CAmbient Temperature Range (F)-4 F to 131 F Ambient Temperature Range (C)-20 C to 55 CEnvironmental, Electrical or Ingress Protection RatingEnvironmental Rating: NEMA2; Environmental Protection Ratings: IP40Maximum Noise Rating35 dB(A) max at 1 m [50 dB (A) for MVN643]Actuator TypeValveFail Safe ModeNon-spring return, Fail in placeTorque Rating (lb-in.)27 lb-in.Torque Rating (Nm)3 NmExternal Auxiliary Switches AvailableNoRotational Stroke Adjustment90° ±3Cable18 AWG, Plenum Rated, 300 V, 10 A, 3 ft. length from end of access cover.Timing, Nominal90 sec. for MVN613 and MVN713; 30 sec. for MVN643Electrical Connections (in.)Field wiring 18 to 20 AWG to screw terminals, located under the removable access cover.
M6410/M7410
Cartridge globe valve actuators are small electric actuators for individual room control that provide floating or modulating control of V5852, V5862 two-way or V5853, V5863 three-way valves.
M6435/M7435
Cartridge globe valve spring return actuators are small electric actuators for individual room control that provide floating or modulating control of V5852, V5862 two-way or V5853, V5863 three-way valves.
Fan Coil Valve Actuators
Humidity resistant fan coil valve actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.