Date:2018-7-10 Hits:3276
Honeywell霍尼韦尔火焰探测器FSL100
FSL100 火焰探測器
FSL100 Series Flame Detectors UV, UVIR, IR3
The FSL100 Series of flame detectors from Honeywell delivers robust, fast and reliable
detection of flaming fires in a wide range of applications.
The range consists of UV, UVIR and IR3 flame detectors. All utilise sophisticated sensing
and signal analysis to detect fires quickly while also rejecting false alarms.
The FSL100 may be small and lightweight for easy installation but they are designed
to work in tough environments both in and out of doors as well as potentially explosive
atmospheres.
With a large field of view they can detect a range of different types of fire including
hydrocarbon and non hydrocarbon sources.
Available in UV, UVIR and 3IR we have your application covered.
Suitable for Many Applications
• UV, UVIR and IR3 available
• Hydrocarbon and non hydrocarbon sources
• Use in potentially explosive atmospheres
• Indoor and outdoor operation
• High visibility red or discrete white models available
Great Performance
• Approved to EN54-10 and FM3260 flame
detector standards
• Comprehensive automatic self test
• Remote manual self test option
Fast & Reliable
• High speed sensors and microprocessor
• Sophisticated analysis algorithms
• Continuous health monitoring
• False alarm rejection
Reduced Life Cost
• Long life elements
• Pressure compensation to avoid contamination
• 2 year warranty
• Buy with confidence
Ease of Installation and Use
• Relay and mA outputs as standard
• Lightweight GRP housing
• Pre-formed knockouts
• Optional swivel mounting bracket
• Long range test lamp available
UV, UV/IR, IR3
Flame Detectors
FSL100-UV
• Suitable for indoor applications, for
example fume hoods and hydrogen
storage areas
• Effective solution for materials burning
with low temperatures, e.g. Sulphur
• Detects fires caused by higher
hydrocarbons (wood, paper, petrol)
as well as hydrogen and lower
hydrocarbons such as methanol
and methane
• Good resistance against the
influences of:
- Direct and reflected sunlight
- Artificial light, such as fluorescent
tubes and glass covered halogen
lamps
FSL100-UVIR
• Analysis of the flame flicker-frequency
for improved false alarm rejection
• Dual sensing methodology enables
a wide range of hydrocarbon and
non-hydrocarbon fires to be
effectively detected
• Monitors higher hydrocarbons flames
(wood, paper, petrol) but also
hydrogen and lower hydrocarbons
such as methanol and methane
• Good resistance against the influences of:
- Direct and reflected sunlight
- Artificial light, such as fluorescent tubes
and glass covered halogen lamps
- Arcs and electric discharges (static
or from e.g. electric motors)
- The radiation from electric welding
provided that the electric welding takes
place at a distance more than 3 meters
from the flame detector (a welding rod
contains organic compounds which
show flame phenomena)
FSL100-IR3
• Analysis of the flame flicker frequency
for improved false alarm rejection
• Particularly suited to liquid
hydrocarbon and dirty fires
• Affected less by window
contamination or smoky fires
• Detects higher hydrocarbons flames
(wood, paper, petrol) and lower
hydrocarbons such as methanol
and methane
• Good resistance against the
influences of:
- Direct and reflected sunlight
- Artificial light, such as fluorescent
tubes and glass covered halogen
lamps
- Arcs and electric discharges (static
or from e.g. electric motors)
- The radiation from electric welding
provided that the electric welding
takes place at a distance more
than 3 meters from the flame
detector (a welding rod contains
organic compounds which show
flame phenomena)
• Especially suitable for smoky fires.
Analysis of the flame flicker frequency
for improved false alarm rejection
Specifications: FSL100 Series Flame Detectors
Ordering Information
Part Number Description
FSL100-UV (red housing) UV flame detector
FSL100-UV-W (white housing) Suitable for ATEX zone 2/22; FM 3611 Class 1, 2 & 3 Div 2
EN54-10 (HIGH sensitivity) certificate
FM3260 approval (pending*)
FSL100-UVIR (red housing) UV/IR flame detector
FSL100-UVIR-W (white housing) Suitable for ATEX zone 2/22; FM 3611 Class 1, 2 & 3 Div 2
EN54-10 (HIGH sensitivity) certificate
FM3260 approval (pending*)
FSL100-IR3 (red housing) Triple IR flame detector
FSL100-IR3-W (white housing) Suitable for ATEX zone 2/22; FM 3611 Class 1, 2 & 3 Div 2
EN54-10 (HIGH sensitivity) certificate
FM3260 approval (pending*)
FSL100-SM21 Swivel mount (White)
FSL100-TL FSL100 test lamp, incl. universal charger and carrying case; safe areas only
FSL100-TLX FSL100 test lamp, incl. carrying case; intrinsically safe; hazardous area