Flame Scanners

Date:2017-10-18     Hits:3614

Fireye 65UV5 self-checking scanners are used to detect ultraviolet emissions from fossil fuel flames such as natural gas, coke oven gas, propane, methane, butane, kerosene, light petroleum distillates and diesel fuels. 

65UV5-1004, 1004E
FLAME SCANNERS


FEATURES INCLUDE:

• Fully integrated design - a true one piece system
• No programming - minimal setting up - ‘out of the box’ operation
• Superb detection, sensitivity and wide angle of view
• Field proven and reliable technology
• Worldwide safety agency approvals
• Rugged NEMA 4X (IP66) housing
• Hazardous Area Classification
• Truly economical solution
• Two versions covering world-wide applications
SPECIFICATIONS
MECHANICAL:
Housing Material: Cast aluminum with black polyester powder coat finish
Housing Weight: 4 lbs (2kg)
Environmental: NEMA 4X, IP66
Mounting: Model 1004: 1" NPT female pipe mount with 3/4" NPT female cooling air connection
Model 1004E: 1" BSP female pipe mount with 3/4" BSP female cooling air connection
Hazardous Classification: Model 1004: Class I Div 2, Groups A, B, C, D, T4A TA = 65°C
Class II Div 2, Groups F & G, T4A TA = 65°C
Model 1004E: Ex II 3 G/D Ex nA IIC T4A
COOLING/ PURGE AIR REQUIREMENTS:
Source: Clean, dry, cool
Volume: 4 SCFM (113 l/min) at 3/4" threaded mounting flange, or 1 inch “Y” fitting,
mounted on scanner sight pipe. Temperature near the upper limit of the scanner operating
range and/or use with dirty/dusty fuels may require up to 15 SCFM (425 l/min)
Pressure: Adequate to overcome furnace or windbox pressure
Temperature Rating: -40° F to + 150°F (-40°C to +65°C)
Humidity: 0% to 95% relative humidity, non-condensing
ELECTRICAL:
Input Power: 24 Vdc, +10%, -15% supply current 100 mA
Electrical Connection: Cable gland and 10 ft (3m) of captive eight conductor cable
Flame Relay Output: SPDT (1 N.O., 1 N.C.)
Fault Relay Output SPST (1 N.O.)
Contact Rating: Minimum: 10 mA @ 5 Vdc
Maximum: 2 A @ 30 Vdc,
2 A @ 240 Vac
Analog Output: 4-20mA dc current, referenced to 24 VDC common, maximum connected load 750 ohms
Status Indication: One (1) internal 2-color LED: “Flame Signal”, “Fault”
INTEGRAL CABLE SPECIFICATION:
Eight (8) Conductors: #18 AWG, color coded
Jacket: PVC, meets UL PLTC Class I, Div 2, no conduit required, UV and Oil resistant
Outside Diameter: 0.383” NOM.
Cable Temperature Rating: -13°F to + 221°F (-25°C to +105°C)
Simplicity Scanner Bulletins
Pub No.
Product
CU-104 Type 65UV5 integrated scanner, 4-290-1, 61-6974, 002608-001 CU-103 Scanner Insulating Jacket & Vortex-tube Cooler Kit 133-771 Electronics assembly replacement procedure for 65UV5-1004ECEX

Service Online
Phone online