The Fireye YZ300 Interlock Annunciator Module provides increased interlock supervision capability of the BurnerLogix System. 

All interlock messages can be programmed using the YZ300P. The Interlock Annunciator Module connects to any YB110 or ZB110 BurnerLogix chassis/amplifier by means of a cable. (P/N ED580-4, ED580-8). A separate wiring base is required 

YZ300 INTERLOCK ANNUNCIATOR
for all BurnerLogix Systems

The FIREYE YZ300 Interlock Annunciator Module provides increased interlock
supervision capability of the BurnerLogix System. The Interlock Annunciator
Module simply connects to any YB110 or ZB110 BurnerLogix chassis/amplifier
by means of a low cost cable.
By wiring any of twenty interlock switches into the Interlock Annunciator Module,
the BurnerLogix display automatically acts as a “first-out” annunciator.
In addition, a fuel selection circuit provides full annunciation even if two fuels
are fired simultaneously!
The YZ300 is shipped with default messages associated with each set of terminals.
LED’s are provided that will blink to indicate what section of the L1-3 and
3-P circuit is open.
Since any interlock message can be modified, the arrangement of interlocks is
your choice, making retro-fits easy!
Messages are modified in one of two ways: select from a built-in library of
messages through the display or program a customized message using
Fireye’s easy to use Windows based YZ300P program. Each custom message
can be up to 40 characters in length. Program messages can be saved to the
user’s PC and recalled later if necessary.
All customized messages are stored in the YZ300. The YZ300 does not require
connection to a BurnerLogix system to be custom programmed.

The wiring bases for the YZ300 (60-2872-1 and 60-2874-1)
measure 4 in. wide by 7 in. tall, consuming a minimum amount
of cabinet space. The wiring bases contain a 24 position terminal
block, each position clearly numbered for easy identification.
Each terminal can accept up to 2 type 14 AWG wires and each
terminal is a clamp type terminal to assure a good mechanical
connection that provides sufficient pressure against the wire.
All BurnerLogix products utilize industry standard ModbusRTU
as the communications protocol. Fireye offers at no
charge the YZ300P to be used for programming custom
messages with any Windows based PC. (Consult Fireye on
how to get it!) Simply click on any interlock position to get
a pop-up dialog box, enter your custom message, click on
the WRITE command and you’re done!
The YZ300P is also used to upload and download messages
to and from the YZ300P. Custom files can be saved and
later retrieved for quick and easy programming.
The YZ300 does not require connection to a BurnerLogix
system for programming.
With Modbus-RTU, each interlock position can be monitored
during burner operation, giving you total control over
system operation.
ORDERING INFORMATION


PART NUMBER DESCRIPTION
YZ300 Interlock Annunciator Module used with the YB110 or ZB110 BurnerLogix chassis/amplifier
60-2872-1 Wiring base, terminal blocks, closed with knockouts
60-2874-1 Wiring base, terminal blocks, open end
ED580-4, -8 YB110 or ZB110 to YZ300 interconnection cable in 4' and 8' lengths
YZ300P Windows based software for programming custom messages


BurnerLogixTM Bulletins
Pub No.
Product
Pub No.
Product
133-675 BurnerLogiX Installation Instructions for 129-178 Remote Display Mounting Kits 133-676 BurnerLogiX Installation Instructions for PigTail Wiring Base for Y type only, 60-2810-1, 60-2812-1, 60-2814-1
133-677 BurnerLogiX Installation Instructions for Terminal Block Wiring Base w/Knockoutsfor Y type only 133-701 BurnerLogiX Installation Instructions for PigTail Wiring Base for Z type only, 60-2850-1,
133-702 BurnerLogix Installation Instructions for terminal block wiring base for Z type only, 60-2852-1, 60-2854-1 133-707 Terminal Block Wiring Base Used with BurnerLogix YZ300 Interlock Annunciator
133-722 Errata Sheet for 61-7161 PowerFlame BLZ-SET BurnerLogix Z Programming/Set-Up Guide
BD-5001 BurnerLogiX Installation Instructions for Displays, BLV512, BLL510 BL-1001 BurnerLogiX Y Modules & Displays, YB110UV, YB110UVSC, YB110IR, YB230UV, YB230UVSC, YB230IR
BLZ-1001 Microprocessor-Based Burner Management Control with Integrated Boiler Control Operation, ZB110UV, ZB110UVSC, ZB110IR BLZPTS-1 Pressure & Temperature Sensors for BurnerLogiX, TS350, TS752, BLPS
YBT-1000 Test Unit for BurnerLogix™ Y Controls, 57YB4-5000 YP-1001 BurnerLogiX YP Programmers, YP100, YP102, YP113, YP138, YP200, YP202, YP300, YP302
YZEM-3001 Interlock Annunciator for use with the Fireye BurnerLogix™ Control, YZ300, 60-2872-1, 60-2874-1 YB110-Spec BurnerLogix Y Product Specification Guide
YZ300P YZ300P windows based software for programming custom messages into the YZ300 BurnerLogix Interlock Annunciator (self extracting zip file) YZ300-Spec Interlock Annunciator for use with BurnerLogix Controls
UC-4851 UC485 Optically isolated USB to RS422/RS485 converter ZB110-Spec BurnerLogix Z Product Specification Guide
133-691 Using Noise Reduction Kit 129-179

Service Online
Phone online