Honeywell Gas Detector About:

Midas gas detector | Sensepoint XCD | FSX Flame Detector | FS10-R FSX Flame Detectors | FS24X Flame Detector | Fire Sentry FS20X | Impulse portable gas detector | Satellite XT | SS4/SS2 Flame Detector | FS7 Flame Detector | HONEYWELL ANALYTICS PORTABLES |


Honeywell Gas Detector

Date:2017-10-20     Hits:2352

Manning AirAlert 96d
Gas Detection Controllers

Acting as the nerve center of a modular gas detection network, this multichannel system provides continuous monitoring of up to 96 sensors.
Features & Benefits
Simple push-button program facilitates adjustment
Supports any combination of Honeywell Analytics gas sensors
Immediate, at-a-glance status
Quick Specs
Supports up to 96 network devices
Easily fine-tune applications ranging from minor operational sequences to reconfiguration of entire network
Simple push-button program facilitates adjustments
Supports any combination of Honeywell Analytics gas sensors, including NH3, CO2, H2, CO, Cl2, CFC’s, HCFC’s, HFC’s, CH4, O2, NO2, and more
Zoning capability allows for up to 126 zones

Immediate At-a-Glance Status


Product Overview


The Manning AirAlertTM 96d multichannel gas monitoring system is designed for installation and operational simplicity for continuous monitoring and control of toxic gases, combustible gases and Oxygen hazards.

The Manning AirAlert™ 96d can support up to 96 sensors and relay modules and provides unique at-a-glance system status and can be maintained with ease using the menu driven push button controls.

This easy to use system can be completely customized in an industrial or commercial application by using any combination of Honeywell Analytics sensors. The Manning AirAlert™ 96d has the potential to complete plant control systems by operating independently, interfacing with it to create a reliable stand-alone safety system.

Additional Features and Benefits:

Applications
Garage Ventilation Control
IAQ Control
Perimeter Monitoring
Refrigerant Leak Detection Monitoring
Zoned Valve Cut-off Control
96 Sensor Capacity

Supports up to 96 network devices
Three distinct channels act as the nerve center of a modular gas detection network
Menu-Driven Program

Easily fine-tune applications ranging from minor operational sequences to reconfiguration of entire network
Simple push-button program facilitates adjustments
Customizable

Supports any combination of Honeywell Analytics gas sensors, including NH3, CO2, H2, CO, Cl2, CFC’s, HCFC’s, HFC’s, CH4, O2, NO2, and more
Field-programmable alarm levels for each sensor
Zoning capability allows for up to 126 zones
Immediate At-a-Glance Status

122 x 32 alphanumeric LCD display provides continuous information for the entire network
Automatic Datalogging Capability

Controller provides automatic datalogging within cast aluminum enclosure
Sensor concentrations and alarms is recorded for analysis
Easy Installation

Cost is reduced by addressable RS-485 MODBUS communication protocol
Installation requires only two pairs of wires to connect each gas sensors and relay modules to one of the controller’s three input channels
Centralized Information

Interface with or function individually with plant control

General Specification
Use Multi-channel gas monitoring system acts as the nerve center of a modular gas detection network, providing continuous
monitoring of up to 96 connected units on three distinct channels.
Common Operation
Display Graphic 122 x 82 alphanumeric dot matrix backlit
Push Button Controls Seven user-friendly pushbuttons easily performs operations from minor fine tuning to reconfiguration of entire network.
Electrical Power 24 VDC, 500 mA (18-36 VDC)
Communication Addressable RS-485 Modbus protocol
Power Supply External M-600400 24 VDC, 6.5 amps, enclosure complies with Nema 4 requirements
Environmental
Operating Altitude Up to 3,000 m (9843 ft.)
Operating Environment Ordinary location
Operational Humidity 0-95% RH (non-condensing)
Temperature -20°C to +50°C (-4°F to +122°F)
Common Module
Communication RS-485: for communication cable, use 24 AWG twisted pair, shielded (Belden #9841 or equal), cable runs up to 2,000 ft. For power cable use
14 AWG
(Belden #5100UE or equal), cable runs up to 1,000 feet.(Belden #5100UE or equal), cable runs up to 1,000 feet.
Network Capacity Up to 96 sensors, 32 per channel Channel 1, 2, and 3
Visual Indicators Power On Green LED
Warn Red LED (blinks upon an event)
Alarm Red LED
High Alarm Red LED
Fault Yellow LED
Tx Amber LED (blinks when used)
Rx Green LED (blinks when used)
Outputs
Relays 4 DPDT relays
5A, 30 Vdc or 250 VAC/30 VDC
Field selectable: energized/de-energized
Red LED for each relay for alarm indication:
One common warn gas alarm
One common alarm gas alarm
One common high gas alarm
One common fault alarm
Communication BACnet output only
Time Delays 0, 30, and 45 seconds, and 1 to 99 minutes before and after alarm
Enclosure NEMA 4x, cast aluminum #A356.0T6, EMI/RFI protected
Over-voltage Category II
Dimensions 24.1 x 35.6 x 8.9 cm (9.50” x 14” x 3.5”)
Weight 5.2 kg (11.4 lbs) 

Service Online